Abstract

The paper presents a calculation method for the SF6 outflow area across the critical cross-section of the nozzle in an HV puffer circuit breaker during the interruption of a short-circuit current. The presence of an electrical arc can cause clogging of the nozzle at the moment when the arc cross section is close to the nozzle throat area. The clogging depends on the instantaneous current value and can cause ablation of the nozzle material. In the long term it can result in a change in the nozzle dimensions which adversely affects the interrupting ability of the circuit breaker.

Authors and Affiliations

Henryk SIBILSKI, Andrzej DZIERŻYŃSKI, Artur HEJDUK, Janusz KURASZKIEWICZ

Keywords

Related Articles

THE DISTRIBUTION OF ERRORS IN THE DESIGN OF INDIRECT LIGHTING WITH SQUARE LUMINAIRES

Square / rectangular luminaires lighting in a lambert way are usually used in large installations of indirect lighting. In order to investigate the operation of the most popular in Poland international programs Relux and...

EFEKTY RADIACYJNE W AKCELERATORACH JĄDROWYCH

W artykule przedyskutowano zagadnienia napromieniowania jonowego występującego w akceleratorach, w których używane są elektromagnesy nadprzewodzące. Omówiono konstrukcję tych urządzeń i znaczenie podstawowych badań fizyc...

CHANGES IN THE REQUIREMENTS OF THE AMENDED EUROPEAN LIGHTING STANDARD

This paper describes the changes in the requirements contained in the new Polish lighting standard BS EN 12464-1 Light and lighting. Lighting of work places. Part 1: Indoor work places that PKN published in the original...

MODELING AND SIMULATIONS OF A NON-LINEAR COIL

Solving rigid differential equations systems should be performed with the application of implicit or semi-explicit methods. As proven in the example given in this paper – the implicit RADAU IIA methods can be successfull...

BADANIA WPŁYWU KONFIGURACJI UZWOJENIA HTS NA ENERGIĘ I ROZKŁAD POLA MAGNETYCZNEGO NADPRZEWODNIKOWEGO ZASOBNIKA ENERGII

Artykuł poświęcony jest nadprzewodnikowemu zasobnikowi energii na przykładzie modelu fizycznego zasobnika zbudowanego w Pracowni Technologii Nadprzewodnikowych Instytutu Elektrotechniki. Rozważany problem dotyczy wyboru...

Download PDF file
  • EP ID EP78973
  • DOI 10.5604/00326216.1210608
  • Views 102
  • Downloads 0

How To Cite

Henryk SIBILSKI, Andrzej DZIERŻYŃSKI, Artur HEJDUK, Janusz KURASZKIEWICZ (2016). CHANGES TO THE SF6 OUTFLOW AREA IN THE NOZZLE OF A HIGH VOLTAGE AUTO-PNEUMATIC CIRCUIT BREAKER DURING A SHORT-CIRCUIT CURRENT INTERRUPTION . Proceedings of Electrotechnical Institute Prace Instytutu Elektrotechniki, 63(273), 25-34. https://europub.co.uk/articles/-A-78973