Damage Analysis of Elbow Fitting at Condenser Air Conditioning Cooling System

Abstract

Elbow fittings is one type of fitting on the piping installation that serves to change the flow direction. With the sudden flow of changes, it will affect the physical condition of the elbow. The flow changes in the elbow will result in changes of flow velocity that affect wall of elbow, the condition will cause erosion corrosion phenomenon. Erosion corrotion is a type of corrosion that uses a mechanical process through the relative movement of the flow and metal. Corrosion erosion can also be caused by impingment corrotion or very rapid flow movement. This study aims to determine the cause of damage elbow by using a CFD simulation and troubleshooting by adding a Vortex Generator or a installed disturber system in the pipeline installation and simulating it again. From the results of research conducted that elbow damage caused by high flow velocity that concerns the outer elbow. The addition of Vortex Generator is proven to be used to reduce excessive flow velocity on erosion-corroded parts. According to the results of the investigation the placement of the most efficient vortex generator if placed at a distance of 0.1 R from elbow inlet.

Authors and Affiliations

Hari Prastowo, Irfan Syarif Arief, Hamzah Fansyuri

Keywords

Related Articles

Comparative Analysis of Probability of Failure Determination Using Weibull Distribution and Generic Failure Frequencies on Heat Exchanger Tube Bundles Based on API 581

RBI analysis for heat exchanger tube has been explained by API 581. Two types of PoF determination using statistical data is provided to determine the PoF category. Both Weibull parameter and generic failure frequencies...

Design of Protection Coordination for Overcurrent on Electrical System in Tanker Ship Plan Using Electro Mechanical Trip Device

Disturbance of power system in ship is unavoidable case that required a function from safety system to separate the affected parts of system. The disturbance in electrical system generally is a short-circuit current. It...

Technical Overview Of Biogas Utilization as Fuel of Boat Engine

The depletion of world energy reserves and the increasing levels of environmental pollution, increase human creativity. Discoveries on environmentally friendly renewable energy-making technologies are increasingly widesp...

The Hull Strength of Marine Current Turbine Platform

Strength analysis of hull structure of marine renewable energy is crucial. The hull structure must be able to whitstand the harsh environmental load such as wave, wind and the weight of the payload and the structure itse...

Analysis Evacuation Route for KM Zahro Express on Fire Condition using Agent Based Modeling and Fire Dynamics Simulatior

Safety is the thing that needs to be preferred by users of transport, passengers should also understand about safety procedures and evacuation procedures in the means of transport. There have been many accidents that hap...

Download PDF file
  • EP ID EP221354
  • DOI 10.12962/j25481479.v1i4.2698
  • Views 220
  • Downloads 0

How To Cite

Hari Prastowo, Irfan Syarif Arief, Hamzah Fansyuri (2017). Damage Analysis of Elbow Fitting at Condenser Air Conditioning Cooling System. International Journal of Marine Engineering Innovation and Research, 1(4), 250-260. https://europub.co.uk/articles/-A-221354