Enhancing the effectiveness of calculation of parameters for short circuit of threephase transformers using field simulation methods
Journal Title: Восточно-Европейский журнал передовых технологий - Year 2018, Vol 4, Issue 5
Abstract
We conducted theoretical research into electromagnetic processes when testing power transformers under the mode of the test short circuit based on a three-dimensional model of the magnetic field in the frequency statement. Reliability and accuracy of determining the parameters for the test short circuit of the power transformer for frequency-domain statements were substantiated with the use of verification of the data of calculation of frequency-domain and time dependent models of the magnetic field for frequency statements. The main regularities of the magnetic field distribution in the volume of the active part of the transformer were determined. In the magnetic field localization zones, 3D intensity distribution is uniform and is determined by the 2D distribution in the horizontal cross section of the active part in the middle of the phase windings height. The values of the axial component of the magnetic field intensity approach 96–97 % of the intensity vector module. An effective approach to field modeling was implemented based on decomposition of the computational domain into spatial zones. Each calculation zone is put in compliance with an electrical circuit of the substitution scheme. Distribution of electric potentials in the horizontal cross-sections of the conductors between the coils or between the turns of windings was accepted as uniform. The superposition of magnetic fields in spatial zones was implemented by means of dynamic synthesis by the criteria of minimal current error for electric circuits of the substitution scheme. The decomposition of the 3D area of field simulation area into the central and end zones is implemented at a distance of 10–15 % of the height of the phase windings, which ensures high accuracy of the magnetic field calculation with the error not exceeding 1.62 %. Time consumption for field simulation of electromagnetic processes under the mode of the test short circuit decreased by 5 times and requirements for the capacity of computing hardware resources decreased by 4 times. High accuracy of identification of parameters of the test short circuit of three-phase transformers was proved by comparing the calculation data to the results of tests at the private company "Eltiz" (Zaporizhzhia, Ukraine). Calculation errors do not exceed 1.42 % for active losses and 1.39 % for short circuit voltage. The proposed approach with the use of the methods of decomposition and of dynamic synthesis makes it possible to significantly improve the effectiveness of the preliminary stage of design preparation of production and can be used for solving the problems of design solutions optimization
Authors and Affiliations
Dmytro Yarymbash, Serhiy Yarymbash, Mykhailo Kotsur, Tetyana Divchuk
Rationale for creating detonation CO2 laser for radioactive surface decontamination
<p>The laser decontamination method is based on the evaporation of oxide films under the influence of radiation. With the evaporation mechanism, laser radiation should heat the upper layer of the film to the boiling poin...
The concept of a modular cyberphysical system for the early diagnosis of energy equipment
<p>We have proposed a concept of the modular cyberphysical system for the early diagnosis of industrial and household power equipment based on the application of approaches and standards of Industry 4.0, in particular th...
Development of the method for rapid detection of hazardous atmospheric pollution of cities with the help of recurrence measures
The method for rapid detection of hazardous pollution of the atmosphere of cities, which is based on dynamic measures of recurrence (repeatability) of the states of the pollution concentration vector, was developed. The...
Studying the load jam modes within the framework of a flat model of the rotor with an autobalancer
<p>This paper reports the analytically investigated load jam modes (balls, rollers, pendulums) within a flat model of the balanced rotor on isotropic elastic-viscous supports carrying the auto-balancer with many identica...
Development of a data acquisition method to train neural networks to diagnose gas turbine engines and gas pumping units
<p>The application of neural networks is one of promising ways to improve efficiency when diagnosing aviation gas turbine engines and gas pumping units. In order to start functioning of such network, it should be trained...