Experimental Research on Power Quality Improvement using Capacitor Bank for 500 kVA Three Phase Transformer

Abstract

This research is to improve the power quality for 500kVA three phase transformer using capacitor bank at Technological University Mandalay . The main purpose of installing a capacitor bank is to compensate the reactive power consumption and reduce the line losses for power quality improvement. The required value of capacitor bank rating for transformer is calculated in this paper. And then the results for loss reduction and reactive power compensation are also compared without and with capacitor bank. In this research, 150 kVAR of capacitor bank is installed to improve the power factor up to 0.99, to decrease reactive power from 138.47 to 0.75kVAR, apparent power from 169.47kVA to 101.93kVA, and percent loss reduction up to 69.14. So, the simple model of reactive power compensation with 150kVAR capacitor bank is helpful for 500 kVA transformer at Technological University Mandalay to reduce reactive power consumption. Phyu Phyu Win | Moe Phyu Thel "Experimental Research on Power Quality Improvement using Capacitor Bank for 500 kVA Three-Phase Transformer" Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-3 | Issue-5 , August 2019, URL: https://www.ijtsrd.com/papers/ijtsrd26637.pdfPaper URL: https://www.ijtsrd.com/engineering/electrical-engineering/26637/experimental-research-on-power-quality-improvement-using-capacitor-bank-for-500-kva-three-phase-transformer/phyu-phyu-win

Authors and Affiliations

Keywords

Related Articles

Load Balancing and Data Management in Cloud Computing

Cloud computing is an online storage media where we access, store and manage the data. It stores the data on remote servers rather than a local server and that data can be accessed through the internet. For example Googl...

Inventory Management System using Struts Framework Architecture

Every rg niz ti n needs invent ry f r sm th running f its tivities. It serves s link between r du ti n nd distribution r esses. The System maintains m uterized inf rm ti n rel ted t the rg niz ti n. Whi h m int ins nd s...

Behavior of Concrete Using Copper Slag As A Strength Parameter in Low Cost Construction Work

The value of concrete in present society cannot be underestimated. We can see concrete structures everywhere, such as buildings, roads, bridges, and dams. There is no escaping the impact concrete makes on your everyday l...

Enhancing the Techniques to Secure Grid Computing

Security is important issue in every aspect in today's world if you are using the networks. Various algorithms are there to secure your network so that unauthorized user can't breach into your accounts. SO for this authe...

Study of The Health Status of Adolescent Boys and Girls (14-16 Years) of D N High School, Anand - Gujarat

Malnutrition continues to be a primary cause of ill health and mortality among children in developing countries. In present study, an attempt was made to find the prevalence of malnutrition (thinness/obesity) among schoo...

Download PDF file
  • EP ID EP628879
  • DOI 10.31142/ijtsrd26637
  • Views 84
  • Downloads 0

How To Cite

(2019). Experimental Research on Power Quality Improvement using Capacitor Bank for 500 kVA Three Phase Transformer. International Journal of Trend in Scientific Research and Development, 3(5), 1202-1207. https://europub.co.uk/articles/-A-628879