LIMITATIONS OF CURRENT OF THE THREE-PHASE ACTIVE POWER FILTER IN THE CONDITIONS OF OVERLOAD AND SHORT CIRCUIT

Abstract

Purpose. The purpose of the work is to develop a method of limiting the maximum allowable level of current of a three-phase active power filter in conditions of overload or short circuit and a system for the implementation of the method. Methodology. For research purposes, the provisions of the pq-theory of instantaneous power, the method of the theory of automatic control in systems with relay controllers, and the methods of simulation in the visual programming environment were used. Results. Both the overloading mode and the short circuit emergency mode, using the proposed solution, do not lead to significant changes in the voltage level on the accumulation capacitor, thus maintaining the stability of the power part of the active power filter. Originality. In the case of temporary overloads of current and short circuits at the network node to which a active power filter is connected, the current's limiting is performed by scaling the current to the level allowed by normal operation of the semiconductor elements of the device, which allows the basic operating algorithm to be implemented in the specified modes. Practical value. The proposed solution can be used as a mean to protect the power part of the device in case of overload, which, in the event of emergencies, and their elimination will automatically restore the normal mode of the device.

Authors and Affiliations

R. V. Vlasenko, O. V. Bialobrzeski

Keywords

Related Articles

AN IMPROVED CONTROL ALGORITHM FOR «DYNAMIC CAPACITOR» VAR COMPENSATOR

Purpose. Modern approaches of VAR compensation are: using compensators with stepped regulation, STATCOMs, active pow-er filters. Recently, more attention is paid to VAR compensator’s design based on the direct AC / AC co...

THE EXPERIMENTAL VALIDATION OF THE GROUNDING DEVICE RESISTANCE MEASUREMENT METHOD

Purpose. The paper considers experimental research of three-electrode units for measuring the resistance of grounding devices for different purposes. Methodology. The experimental study of the method of resistance measur...

THE PHASE REACTOR INDUCTANCE SELECTION TECHNIQUE FOR POWER ACTIVE FILTER

Purpose. The goal is to develop technique of the phase inductance power reactors selection for parallel active filter based on the account both low-frequency and high-frequency components of the electromagnetic processes...

SCREENING MAGNETIC FIELDS OF THE POWER FREQUENCY BY THE WALLS OF HOUSES

Purpose. To investigate the effectiveness of the screening of the magnetic field at 50 Hz by the walls of house. Methodology. To study the effectiveness of the screening we used the measurements of the magnetic field 1)...

THREE-ELECTRODE AIR SWITCHBOARD WITH THE GRAPHITE ELECTRODES OF KATG-50 ON VOLTAGE TO ±50 KV AND IMPULSE CURRENT BY AMPLITUDE TO ±220 KA

Purpose. Development and creation of the simplified construction of a high-voltage heavy-current air three-electrode switchboard with graphite electrodes, intended for operation in composition the powerful generator of l...

Download PDF file
  • EP ID EP483758
  • DOI 10.20998/2074-272X.2018.1.04