THE OFF-LINE DIAGNOSE OF AUTOMATIC CIRCUIT BREAKERS BY THE TIME DOMAIN AND FREQUENCY VIBRATION ANALYSIS

Journal Title: ANALELE UNIVERSITATII DIN CRAIOVA - Seria Inginerie electrica - Year 2010, Vol 34, Issue 34

Abstract

This paper presents a methodology for determining the operation time at opening and closing of the circuit breakers, using multi-channel sound and vibration analyzers. All the tests on the circuit breaker are made according the prescriptions of normative [3]. It is noteworthy that all tests prescribed by normative [3] are based on preventive diagnosis. This paper approaches the issue of predictive diagnosis of circuit breakers by proposing an original method of comparing the "witness pattern" to "actual pattern" by the Dynamic Time Warping algorithm (DTW). This algorithm is developed by the Megger Company from Sweden and use FFT frequency analysis and time domain analysis. To determine the speed and time of closing-opening for circuit breakers, the authors used sound and vibration analyzer Svan 958, which has triaxial accelerometers for vibration measurements, and offers the opportunity to make independent measurements on three phase. Using the multi-channel analyzer in diagnosis of circuit breakers, have the following advantages: enable the opening and closing times determining; by comparing the amplitude-time characteristics can be determined the non simultaneity of phases L1, L2 and L3; the setting possibilities of the SVAN 958 analyzer to determine acceleration, velocity or displacement, allow dynamic behavior analyzing; the frequency analysis by selecting 1/1 octave or 1/3 octave allows the analysis simplification by the method of Dynamic Time Warping in the predictive diagnosis procedures of circuit breakers.

Authors and Affiliations

Horia BĂLAN, Aurel BOTEZAN, Mircea BUZDUGAN, Elena STEFAN, Gabriel PIRV, Petros KARAISSAS

Keywords

Related Articles

Estimation of Certain Power in Single-phase Network and DC Circuits

Requirement of electrical energy is in order to operate various domestic and industrial devices like ap-pliances, equipment and machinery. Electrical energy per time unit represents electrical power transferred. Well kno...

The influence of ambient temperature on the potentiality of integrated systems for wind energy conversion into electricity

The main purpose of this paper is to view the influence of ambient temperature on the magnetic vector potential of a particular data structure, and thus the magnetic field distribution within the structure. The secondary...

DEVELOPMENT, MANUFACTURE AND TESTING OF HORIZONTAL AXIS WIND MICROTURBINES WITH POWER OF 10 KW

Under the circumstances of the total energetic recourses deficit in the Republic of Moldova appears the problem of non-traditional sources utilization recovered by energy. Important sources of renewable energy are the wi...

EXPERIMENTAL DETERMINATION OF PARAMETERS DESCRIPTIVE OF MAGNETO-RHEOLOGICAL VALVE

In this paper is presented an experimental test stand of rheological stop-valves. Rheological stop-valve structures are robust, simple in terms of constructive and easy to control. However, due to non-Newtonian fluid flo...

The Resistive Tubular Heater - Mathematical and Simulation Model

It is essential to achieve the mathematical model and the simulation when designing complex installations. This allows the analysis of different operating modes and the behavior of the existing system. It enables notific...

Download PDF file
  • EP ID EP139639
  • DOI -
  • Views 176
  • Downloads 0

How To Cite

Horia BĂLAN, Aurel BOTEZAN, Mircea BUZDUGAN, Elena STEFAN, Gabriel PIRV, Petros KARAISSAS (2010). THE OFF-LINE DIAGNOSE OF AUTOMATIC CIRCUIT BREAKERS BY THE TIME DOMAIN AND FREQUENCY VIBRATION ANALYSIS. ANALELE UNIVERSITATII DIN CRAIOVA - Seria Inginerie electrica, 34(34), 113-118. https://europub.co.uk/articles/-A-139639