Voltage Quality Improvement with Shunt Bank Capasitor and Transformer Tap
Journal Title: Engineering and Technology Journal - Year 2024, Vol 9, Issue 08
Abstract
Morocco Feeder Tapung Department is 20 kV feeder with the largest voltage drop in the PT. PLN (PERSERO), ULP Duri. The voltage drop was 16% of the nominal voltage. This study conducted voltage repairs on the medium and low voltage sides to strive for voltage increase to achieve standardization. The first stage of repair was to increase the tap by 5% on the secondary side of the Unit 1 distribution transformer of the Balai Pungut Substation. The second stage of repair was by placing a shunt capacitor bank with a capacity of 400 kVAR on bus 172. The third stage of repair was by increasing the tap of transformer by 2.5% and 5% on the secondary side of 32 and 13 distribution transformers. The result, after simulating the lowest voltage value on the medium voltage network is 91.69% and on the low voltage network is 90.47%. So that the voltage value obtained after performing the above repair measures resulted in voltage repair that has met the standard SPLN 1: 1987 which is 5 % and -10% against nominal voltage.
Authors and Affiliations
Liliana ,Zulfatri Aini , Sepannur Bandri,
ENHANCING THE ENERGY EFFICIENCY OF WBAN SENSOR NODES BY EMPLOYING FUZZY LOGIC TECHNIQUE
Restricted size of the battery results in limited energy storage and various other problems likely. So the sensors should be properly used during their energy use, as their batteries are not to be replaced quite often. E...
ECG ARRHYTHMIA CLASSIFICATION USING A CONVOLUTION NEURAL NETWORK
In this research paper, we propose a method for electrocardiogram (ECG) arrhythmia classification using a convolutional neural network (CNN). CNN has established to have a great performance in ECG classification and patt...
Analyzing Disaster Risk Reduction (DRR) Policies and Their Effectiveness in Reconstruction Efforts
Disaster Risk Reduction (DRR) policies play a crucial role in mitigating the impact of disasters and ensuring effective reconstruction efforts. Due to the increasing frequency and intensity of natural disasters particula...
Delay Compensation Model in 100mbps Switched Ethernet Using Sliding Mode Controller (SMC)
In the realm of networked systems, achieving timely and reliable communication is paramount, particularly in high-speed environments like 100Mbps Switched Ethernet networks. However, inherent delays in communication chan...
BEHAVIOUR OF REINFORCED CONCRETE BEAM STRENGTHENED WITH GFRP
To carry out studies some experimental investigations were done on behaviour of RC beams strengthened in flexural and shear by means of GFRP laminates. Outwardly epoxy-bonded GFRP sheets reinforced concrete beams were te...