The pulse method may be used to measure the footing resistance of transmission towers with overhead grounding wires. Measuring systems that obtain the time dependent transient impedance may be used to measure the low-frequency resistance of transmission tower grounding devices. Current pulse generators with rectangular pulse shape are used in the measuring systems. The current pulses must have short rising time and constant magnitude during a measurement interval. Experimental investigations have shown that a pulse generator with inductive energy storage may be used in the measuring system. Generators with inductive energy storage have a number of advantages over pulse generators with capacitive energy storage. Namely, in case of unevenly distributed surge impedance along the current lead or in case of reflections from the remote end of the current lead an inductive generator allows to form a current pulse with a constant shape. Inductive pulse generators have high pulse energy. So, they may be used to measure the grounding resistance in high soil resistivity areas. Measuring systems based on an inductive storage pulse generator may be used not only to measure the footing resistance of transmission towers; they can also be used for experimental investigation of the effectiveness of lightning protection systems, in particular to obtain the parameters of RLC equivalent circuit of a single grounding device. Two possible topologies of an inductive pulse generator output stage have been considered in the paper. In the first case a step-up transformer is used as energy storage and an IGBT is used as opening switch. In another case an inductor is used as energy storage and MOSFETs are used as opening and closing switches. The experimental current waveforms for both types of generators have been given. They show that an inductor based pulse generator has better characteristics. Therefore it is preferred for this application.
Authors and Affiliations
V. V. Kolobov, M. B. Barannik, V. N. Selivanov
Method for determining the quality of cable inlets sealant using infrared thermography
The results of applying the quality control method to cable inlets sealant (hermetic lead, sealed lead-in, cable boxes) have been considered. Cable inlets are designed to prevent the spread of fire in adjacent areas thro...
The inclusion of grothite in the zircon from granitoids of the crystalline basement of the Southern Yamal Peninsula
Grothite – rare F-Al-rich type of titanite – has been found in accessory zircon from the granitoids of the pre-Jurassic basement of the Verkhnerechensky oil-gas area (in the southern part of the Yamal Peninsula) as a res...
The history of decisions on creation of nuclear and metallurgical complex on the basis of the Kola nuclear power plant
Some reasons for the choice of directions for using electric and thermal energy of the Kola nuclear power plant located beyond the Arctic Circle have been presented. The regions of the country and their large-scale indus...
Phytobenthic communities of the Barents Sea Arctic zone and climate change
The study of species structure of benthic seaweeds populations in plant communities of the coastal Arctic zone of Arctic archipelagoes of the Barents Sea on the basis of expeditionary works' materials has been carried ou...
Sequence of REE-Th-U minerals in the Litsa uranium ore area (the Kola Region)
Mineralogical and petrographic study of REE-Th-U mineralization in rocks of the Litsa uranium ore area has been carried out to detail the sequence of formation of rare-earth, uranium and thorium minerals in rocks. The st...