Conversion Conditions for Fixed Temperature Difference with Variable Water Supply Temperature and Large Temperature Difference Control Strategies in Urban Rail Transit Station Air-conditioning Chilled Water System

Journal Title: Urban Mass Transit - Year 2024, Vol 27, Issue 8

Abstract

Objective To achieve the lowest overall energy consumption of urban rail transit station air-conditioning chilled water system under both fixed temperature difference with variable water supply temperature and large temperature difference conditions, it is necessary to study the conversion conditions between these two control strategies. Method Taking an urban rail transit station in Zhengzhou City as example, a model of air-conditioning chilled water system under the above two conditions is established using TRNSYS (transient system simulation tool) platform. Under the premise of maintaining the required cooling capacity at the terminal end of air-conditioning chilled water system, the impact on system energy consumption is studied in scenarios of a constant chilled water temperature difference with variable water supply temperature (7-12 ℃), and a constant water supply temperature with variable water supply-return temperature difference (5-10 ℃). Result & Conclusion The conversion conditions between the two control strategies are as follows: when the load rate is less than or equal to 40%, the fixed temperature difference with variable water supply temperature control strategy is more energy-efficient; when the load rate exceeds 50%, the large temperature difference control strategy is more suitable. These conversion conditions not only meet the comfort requirements of station personnel, but also achieve the goal of combined control strategy regulation, ultimately reducing the overall energy consumption of air-conditioning chilled water system.

Authors and Affiliations

Sanxian XIA, Shaochen ZHANG, Weizhi YU, Jie LAN, Dasi HE

Keywords

Related Articles

Architecture Design Scheme of Signal Centralized Monitoring System Based on Cloud Computing Technology

[Objective] To meet the development needs of railway electricity work monitoring services and address issues such as high coupling degree, lengthy deployment time, and high construction and operational costs in conventio...

Influencing Factors of Shield Tunnel Segment Floating in Muddy Siltstone Stratum

Objective When shield tunnels crossing water-rich muddy siltstone stratum, the phenomenon of multi-ring tunnel segment overall floating often occurs, leading to quality defects such as segment damage, misalignment, and a...

Method for Restoring Urban Rail Transit Passenger Spatio-Temporal Paths in Consideration of Congestion

Objective Passenger flow is the pillar for operation and management of urban rail transit. With the increasing development of urban rail transit, the demand for meticulous and accurate passenger flow analysis is getting...

Influence of Brake Device Push-out Stiffness on Vibration Performance of Rail Transit Vehicle

Objective As a braking mode,electromechanical brake adopts the motor controlled screw rod drive to implement the pushing action, making the brake shoe to contact with the wheel and complete the transmission of brake forc...

Research on Reactive Power Coordination Control Scheme of Energy Feedback Device in Urban Rail Transit Power Supply System

Objective Currently, the urban rail transit power supply system mainly relies on the main substation SVG (static var compensator) for reactive power compensation. During non-operating hours at night, the medium voltage l...

Download PDF file
  • EP ID EP742716
  • DOI 10.16037/j.1007-869x.2024.08.045
  • Views 13
  • Downloads 0

How To Cite

Sanxian XIA, Shaochen ZHANG, Weizhi YU, Jie LAN, Dasi HE (2024). Conversion Conditions for Fixed Temperature Difference with Variable Water Supply Temperature and Large Temperature Difference Control Strategies in Urban Rail Transit Station Air-conditioning Chilled Water System. Urban Mass Transit, 27(8), -. https://europub.co.uk/articles/-A-742716