Failure Occurrence Probability Assessment of Claus Furnace Package in Sulfur Recovery Unit Using Fault Tree Analysis Based on Conventional and Fuzzy-Based Approach

Journal Title: UNKNOWN - Year 2018, Vol 10, Issue 2

Abstract

Background: If shutdown scenario of burner of the sulfur recovery unit takes place, toxic release, fire, and explosion accident can easily occur. Therefore, it is essential to assess the basic causes of burner shutdown scenario. Fault Tree Analysis (FTA) could be used to assess the occurrence probabilities of burner shutdown scenario and its basic causes/events. The failure occurrence probability of these Basic Events (BE) are often not available in lack of data and uncertain conditions. Objectives: This study was done to provide a comprehensive approach for analyzing and calculating BE failure occurrence probability affecting the shutdown scenario, using combined fuzzy logic, expert judgment, and FTA. Methods: The study was carried out from June to December, 2016. In this study, a fuzzy-based approach based on expert judgment was proposed to calculate the occurrence probability of burner shutdown scenario in lack of data and uncertain conditions. The brainstorming and FMEA, and HAZOP study were first used to identify fault events of the fault tree. Then, based on these methods, the fault tree was constructed. Subsequently, the failure occurrence probabilities of BE and shutdown scenario were calculated using the fuzzy-based approach and a conventional approach. Finally, the Fussell-Vesely importance analysis was used to rank the BE in FTA. Results: Results showed that the occurrence probability of shutdown scenario was 4.76E-04 per year. Since the failure occurrence probabilities of some BEs were not available, using failure probability functions in the conventional approach cannot provide failure occurrence probabilities of those BE. Therefore, the occurrence probability of shutdown scenario based on the conventional approach was not available. Based on the Fussell-Vesely importance measure analysis, it was determined that the blower failure while running, air pre-heater blockage, and shut-off valve fail close were 3 major causes of “burner shutdown scenario”. Conclusions: The fuzzy-based approach could derive a failure occurrence probability of BE based on expert subjective judgments using the failure possibility distributions (FPDs) in lack of data conditions. This study overcame the weaknesses of the conventional approach, to calculate BE failure occurrence probabilities via fuzzy logic.

Authors and Affiliations

Abbas Bakbaki, Nader Nabhani, Bagher Anvaripour, Gholamabbas Shirali

Keywords

Related Articles

Clinical Manifestations and Laboratory Findings of Brucellosis at Boo-Ali-Siena Hospital of Ghazvin Province of Iran

Background: Brucellosis as a zoonotic disease is controlled in many developed countries though it still remains endemic in the majority of Middle Eastern and developing countries. Objectives: The purpose of this study w...

Evaluation of Cadmium Concentration in Wheat Crop Affected by Cropping System

Background: Cadmium accumulation is a growing problem for foodstuff and the environment; it has negative impacts on humans including the damage to kidneys and liver tissue, as well as carcinogenesis, and emphysema. Obje...

An Artificial Neural Network - Particle Swarm Optimization (ANN- PSO) Approach to Predict Heavy Metals Contamination in Groundwater Resources

Background: The quality of groundwater as the most important source for domestic, irrigation, and industrial purposes is affected by discharge of the chemicals from the anthropogenic resources. Therefore, the current stu...

Occupational Exposure of Train Drivers to Static and Extremely Low Frequency Magnetic Fields in Tehran Subway

Background: Electrification of transport systems currently deserves top priority in Iran. Such systems generate a magnetic field in static or extremely low frequency ranges. Therefore, train drivers may be exposed to the...

Survey of Knowledge and Attitude Toward Emergency Contraceptive Method Among Married Women in Reproductive Age Group

Background: Unwanted pregnancy (UP) is a worldwide problem. UP mainly results from the improper or lack of use of effective contraceptive methods. Hormonal emergency contraceptive (EC) is a method of family planning that...

Download PDF file
  • EP ID EP292528
  • DOI 10.5812/jjhs.58162
  • Views 61
  • Downloads 0

How To Cite

Abbas Bakbaki, Nader Nabhani, Bagher Anvaripour, Gholamabbas Shirali (2018). Failure Occurrence Probability Assessment of Claus Furnace Package in Sulfur Recovery Unit Using Fault Tree Analysis Based on Conventional and Fuzzy-Based Approach. UNKNOWN, 10(2), 1-10. https://europub.co.uk/articles/-A-292528