Field Effects on Multiple Particle Contamination And Breakdown Voltage Inside Gas Insulated Bus Duct.

Abstract

The metallic particle contamination in the Gas-Insulated Systems (GIS), plays a key role for the occurrence of Partial Discharge (PD), which causes the failure of insulation in the GIS. This paper presents the study of field effects on multiple particle contamination and breakdown voltage initiated by metallic particles inside a gas insulated bus duct filled with SF6 gas. In this paper, A single Phase Gas Insulated Bus duct with inner diameter conductor of 55mm and diameter of enclosure 150 mm is considered. Three metallic Particles of size of 10 mm in length and 0.25 mm radius, 10 mm length and 0.15 mm radius and 7 mm and 0.25 radii are considered to be present in the GIB. the Finite Elements Method is used to evaluate the electric field distributions on and around the metallic particles at different positions of the particles like when resting on the enclosure and particles floating inside the gap. Electric field intensity in the GIS are studied for both single particle and multiple particles at a time. The breakdown voltages for both single and multiple particle contamination are determined. The effect of gas pressure on the breakdown voltages also studied.

Authors and Affiliations

Ranuva Nageswara Rao, Dr. S. S Tulasiram

Keywords

Related Articles

Object Recognition Approaches

Every Field of Computer Science from Robotics to Artificial Intelligence demand the system which have the ability like we human being have to recognize different things basis on certain properties of objects such as colo...

Fault Diagnosis usingImproved Ant Colony Optimization Algorithm

:In this paper a novel method for solving diagnostic problems more effectively was designed by using a soft computing method. Firstly, vibration signal was measured and analyzed, secondly, the diagnostic tasks were solve...

Non-Linear Water Wave Equation Time Series Formulated Using Velocity Equation as the Result of Laplace Equation

This article developed a model of time series wave where during the formulation velocity equations as the result of Laplace theory was done. As the result of this method, the continuity equation was substituted to moment...

Survey Paper on Captcha Using Different Methods And Techniques

The internet has been enjoying associate more and more vital role in our way of life, with the supply of the many web services comparable to email and search engines. CAPTCHA (Completely machine driven Public Turing take...

Packed Bed Column Studies for the Removal Of Reactive Red Dye Using ECH Cross linked Chitosan Beads

Dyes are coloured substances that have an affinity to the substrates on which they are applied. The dye is generally applied in an aqueous solution, and requires a mordant to improve the fastness of the dye on the fiber....

Download PDF file
  • EP ID EP392056
  • DOI 10.9790/9622-0708046671.
  • Views 107
  • Downloads 0

How To Cite

Ranuva Nageswara Rao, Dr. S. S Tulasiram (2017). Field Effects on Multiple Particle Contamination And Breakdown Voltage Inside Gas Insulated Bus Duct.. International Journal of engineering Research and Applications, 7(8), 66-71. https://europub.co.uk/articles/-A-392056