IMPROVING CALCULATION ACCURACY OF CURRENTS IN CABLE SHIELDS AT DOUBLE-SIDED GROUNDING OF THREE-PHASE CABLE LINE

Abstract

This paper deals with the calculation of currents in shields of single-core cables at double-sided grounding of three-phase cable lines. We consider flat and trefoil cable lines and receive the analytical expressions for RMS currents in the shields of cables. These expressions allow reducing the shield current calculation error to value of 5 %. We analyze the known approximate expressions for RMS currents in the shields of cables and represent dependencies of corresponding calculation errors on cable line dimensionless parameters. These dimensionless parameters are determined by the distance between the axes of the cables, the radius and the resistance of shields.

Authors and Affiliations

V. S. Grinchenko, O. O. Tkachenko, N. V. Grinchenko

Keywords

Related Articles

MULTIFREQUENCY ALGORITHMS FOR DETERMINING THE MOISTURE CONTENT OF LIQUID EMULSIONS BY THE METHOD OF RESONANCE DIELCOMETRY

Purpose. The main attention is paid to the development and investigation of multifrequency algorithms for the realization of the method of resonance dielcometric measurement of the humidity of emulsions of the type «nonp...

CHARACTERISTICS OF SPECIALIZED SINGLE-PHASE HIGH VOLTAGE DOUBLER RECTIFIER

Introduction. To obtain a high voltage direct current, voltage multipliers with a number of cascades of three or more are widely used. At the same time, for voltage levels of 100…200 kV there are several advantages of us...

COMPUTER SIMULATION OF INTERMITTENT CURRENT MODE OF DC ELECTRIC DRIVE WITH THREE-PHASE CONTROLLED RECTIFIER

Introduction. The mode of intermittent current for DC motor with three-phase thyristor rectifier appears in the idle intervals of some mechanisms. Active and passive filters reduce the variable component of the rectified...

NUMERICAL FIELD ESTIMATION OF TURBOGENERATOR STATOR WINDING SHORTENING EFFICIENCY

On the basis of numerical calculations of rotating magnetic field, a turbogenerator is evaluated for cases of a shortened stator winding and a diametric one. The parameters compared are the shape and harmonic composition...

AN ANTHOLOGY OF THE DISTINGUISHED ACHIEVEMENTS IN A SCIENCE AND TECHNIQUE. PART 24: SUBJUGATION OF EARTHLY DRY LAND AND WORLD OCEAN

A short essay of world history of subjugation and study by humanity of earthly continental dry land and enormous marine spaces of Earth is presented.

Download PDF file
  • EP ID EP292114
  • DOI 10.20998/2074-272X.2017.2.06
  • Views 95
  • Downloads 0

How To Cite

V. S. Grinchenko, O. O. Tkachenko, N. V. Grinchenko (2017). IMPROVING CALCULATION ACCURACY OF CURRENTS IN CABLE SHIELDS AT DOUBLE-SIDED GROUNDING OF THREE-PHASE CABLE LINE. Електротехніка і Електромеханіка, 0(2), 39-42. https://europub.co.uk/articles/-A-292114