Pollution Maintenance Techniques in Coastal High Voltage Installations

Journal Title: Engineering, Technology & Applied Science Research - Year 2011, Vol 1, Issue 1

Abstract

Pollution of outdoor high voltage insulators is a common problem for utilities, with a considerable impact to power system reliability. In an effort to prevent possible flashovers due to pollution, many methods have been applied, aiming to improve the insulation performance, either by suppressing the formation of surface conductivity or by increasing the possible insulation level. In the case of substations, the selection of the appropriate technique is complex due to certain issues correlated to the nature of the installation. In this paper, several techniques usually implemented by utilities, are investigated based on the experienced gained in the case of Crete, a Greek island in southern Europe, where due to the coastal development of the power system, the majority of high voltage installations are exposed to intense marine pollution. The technique of coating insulators with Room Temperature Vulcanized Silicone Rubber (RTV SIR) has proved rather efficient and therefore is presented extendedly. Correlation of the material behaviour with environmental conditions is discussed and results from long term monitoring, including environmental parameters and leakage current measurements, in a 150 kV Substation are presented. It is shown that RTV SIR coatings have remarkably suppressed surface activity and that porcelain insulators exhibit different activity period when coated.

Authors and Affiliations

K. Siderakis, D. Pylarinos, E. Thalassinakis, I. Vitellas, E. Pyrgioti

Keywords

Related Articles

A Low Cost Automated Weather Station for Real Time Local Measurements

In this paper, we present an automated weather station for real time and local measurements, based on an embedded system that continuously measures several weather factors such as temperature, humidity, barometric pressu...

Potential Recovery of Silver (Ag) from X-ray Fixer Waste by Alkaline Treatment

The study aims to establish a chemical method of silver recovery from x-ray processing fixer waste by alkaline treatment using sodium hydroxide (NaOH). The samples used in the study were collected from selected hospitals...

Quality Improvement of a Small Water Supply. A Practical Application of a Full System of Nanofiltration

The THM level in the Spanish drinking water is limited to less than 0.100 mg/L, due to its potential toxicological effect on humans. This paper investigates the comparison of the results obtained in a small supply of wat...

Motivation Factors for Adopting Building Information Modeling (BIM) in Iraq

Building information modeling (BIM) is an integrated and comprehensive system including whatever is related to a construction project and its stages. It represents a unified database for all project data through which pr...

Accuracy of Bit Error Probability for W-CDMA System Using Code Tree

W-CDMA is radio access utilized for 3G cell frameworks. A code tree allocation scheme is one of the most explored channelization techniques, used to improve system performance and capacity through adjustable data rates....

Download PDF file
  • EP ID EP84372
  • DOI -
  • Views 364
  • Downloads 0

How To Cite

K. Siderakis, D. Pylarinos, E. Thalassinakis, I. Vitellas, E. Pyrgioti (2011). Pollution Maintenance Techniques in Coastal High Voltage Installations. Engineering, Technology & Applied Science Research, 1(1), -. https://europub.co.uk/articles/-A-84372