SOIL RESISTIVITY INVESTIGATIONS FOR SUBSTATION GROUNDING SYSTEMS IN WETLAND REGIONS – A CASE STUDY OF LAGOS STATE, NIGERIA

Journal Title: ASIAN JOURNAL OF NATURAL & APPLIED SCIENCES - Year 2017, Vol 6, Issue 4

Abstract

Soil resistivity - a measure of how much the soil resists the flow of electricity is a critical factor in the design of safe and efficient grounding systems. Actual resistivity measurements are required to fully qualify soil resistivity and its effects on any proposed substation grounding system. This paper investigated the soil resistivity in three different sites in Lagos – a wetland region in Nigeria during the wet and dry seasons of 2016 in line with the relevant IEEE Standards and International best practices for determining resistivity levels for substation grounding system designs. To locate the soil of acceptable resistivity values that would ensure effective grounding system design for substations in the region, the Wenner Four-Pin Method was deployed. The findings show that soil resistivity in wetland areas varies according to seasons being significantly high during the dry seasons and significantly low during the wet seasons. The outcome of this study is useful for purposes of estimating the ground resistance and potential gradients including step and touch voltages of substation grounding installations and for computing inductive couplings between neighboring power and communication circuits within and around wetland regions.

Authors and Affiliations

Hachimenum Nyebuchi Amadi

Keywords

Related Articles

 PREPARATION AND CHARACTERIZATION OF ACTIVATED CARBON FROM FLUTED PUMPKIN (TELFAIRIA OCCIDENTALIS HOOK.F) SEED SHELL

 Ten samples of activated carbon were successfully prepared by carbonization and activation of fluted pumpkin seed shell. Thermal activation was achieved at 300°C, 400°C, 500°C, 600°C and 700°C, while chemical act...

IONOSPHERIC ANOMALY FROM HUGE GAS EXPLOSION IN KAOHSIUNG CITY IN TAIWAN ON 31 JULY 2014

This paper used two-dimensional Principal Component Analysis (2DPCA) to determine total electron content (TEC) respond in the ionosphere for the huge gas explosion in Kaohsiung, Taiwan at 15: 59 (UT) on 31 July 2014. Res...

SOIL RESISTIVITY INVESTIGATIONS FOR SUBSTATION GROUNDING SYSTEMS IN WETLAND REGIONS – A CASE STUDY OF LAGOS STATE, NIGERIA

Soil resistivity - a measure of how much the soil resists the flow of electricity is a critical factor in the design of safe and efficient grounding systems. Actual resistivity measurements are required to fully qualify...

Leakage Current Test at Household Refrigerator Type Urg-129 Base Standard Nasional Indonesia (Sni) 04-6292.2.24-2001 For Safety Equipment

Leakage current testing is one of the types of electrical safety test, where test is intended to determine the level of security of an electronic product in this refrigerator URG - 129. Testing is done by giving some dif...

The Effectiveness of Logo-Bibliotherapy on the Depression of Selected Filipino Suffering from Myasthenia Gravis

Myasthenia Gravis (MG), a chronic autoimmune neuromuscular disease characterized by weakness of the skeletal muscles of the body caused by circulating antibodies that block acetylcholine receptors at the post-synaptic ne...

Download PDF file
  • EP ID EP574304
  • DOI -
  • Views 93
  • Downloads 0

How To Cite

Hachimenum Nyebuchi Amadi (2017). SOIL RESISTIVITY INVESTIGATIONS FOR SUBSTATION GROUNDING SYSTEMS IN WETLAND REGIONS – A CASE STUDY OF LAGOS STATE, NIGERIA. ASIAN JOURNAL OF NATURAL & APPLIED SCIENCES, 6(4), 90-99. https://europub.co.uk/articles/-A-574304