Abstract

At three locations in Zagreb, classical and extended thermal response test (TRT) was conducted on installed coaxial heat exchangers. With classic TR test, thermogeological properties of the ground and thermal resistance of the borehole were determined at each location. It is seen that thermal conductivity of the ground varies, due to difference in geological profile of the sites. In addition, experimental research of steady-state thermal response step test (SSTRST) was carried out to determine heat rejection rates for passive and active cooling in steady state regime. Results showed that heat rejection rate is only between 8-11 W/m, which indicates that coaxial system is not suitable for passive cooling demands. Furthermore, the heat pump in passive cooling mode uses additional plate heat exchanger where there is additional temperature drop of working fluid by approximately 1,5 °C. Therefore, steady-state rejection rate for passive cooling is even lower for a real case project. Coaxial heat exchanger should be always designed for an active cooling regime with an operation of a heat pump compressor in a classical vapour compression refrigeration cycle.

Authors and Affiliations

Tomislav Kurevija, Marija Macenić, Kristina Strpić

Keywords

Related Articles

ANALIZA RADARSKE PROCJENE OBORINA U SREDIŠNJOJ HRVATSKOJ

Dobro praćenje oborine od velike je važnosti u mnogim granama ljudskoga djelovanja koje se koriste meteorološkim informacijama. Oborina je varijabilna u vremenu i prostoru te je zato poželjno primjenjivati alate koji osi...

KATEGORIZACIJA PODZEMNIH RADOVA PO METANU

Podzemni rad, pri kojem nema ili su prisutne male količine metana postojećim postupkom kategorizacije, svrstava se u nemetanski režim rada. Teškoće pri definiranju izvorišta plina. posebice kada postoji mogućnost napajan...

RUDARSKI PODUZETNICI U HRVATSKOJ OD SREDINE XIX. DO SREDINE XX. STOLJEĆA

Gospodari, ili posjednici rudarskog prava za istraživanje ruda bili su rovitelji i samostalni (slobodni) rovitelji. O posjednicima rudnih polja ili rudnika vođene su podjelbene knjige i registri u kojima je upisano, medu...

OTVORENI SUSTAV POTPORE PROSTORNOM ODLUČIVANJU NA PRIMJERU ODABIRA LOKACIJE ODLAGALIŠTA RADIOAKTIVNOG OTPADA

U posljednje vrijeme se u znanstvenim i stručnim krugovima učestalo raspravlja o pronalasku odgovarajuće lokacije za odlaganje radioaktivnog otpada. Ulaskom Republike Hrvatske u Europsku Uniju tema će se još više aktuali...

FORMATION MECHANISMS OF FE-MN CONCRETIONS IN THE VIJENAC QUARRY, DINARIC OPHIOLITE ZONE

Vijenac quarry, near Tuzla in Bosnia-Herzegovina, is composed of carbonate rocks locally embedding tectonically disturbed siltite and sandstone with Mn-Fe concretions. The quarry itself represent a part of Dinaric overst...

Download PDF file
  • EP ID EP30203
  • DOI 10.17794/rgn.2018.2.6
  • Views 206
  • Downloads 5

How To Cite

Tomislav Kurevija, Marija Macenić, Kristina Strpić (2018). STEADY-STATE HEAT REJECTION RATES FOR A COAXIAL BOREHOLE HEAT EXCHANGER DURING PASSIVE AND ACTIVE COOLING DETERMINED WITH THE NOVEL STEP THERMAL RESPONSE TEST METHOD. UNKNOWN, 33(2), -. https://europub.co.uk/articles/-A-30203